SANKALPELECTRICALS Enquiry listList

Elmeasure · Circuit protection

Elmeasure CURO Surge Protection Device

Price on enquiry

DIN-rail surge protection devices for AC and DC systems against lightning and switching surges.

Sankalp Electricals is an authorised channel partner of Elmeasure.

Or call +91 98203 16440

Key features

  • Type 2 AC, Type 1+2 AC and Type 2 DC (solar PV) versions
  • Response time less than 25 ns
  • Visual status indication window (green ok / off defect)
  • Built-in thermal protection
  • Compact modular design for 35 mm DIN rail
  • Optional remote signalling contacts

Applications

  • Main distribution boards and sub-panels (Type 2 AC)
  • Solar PV string boxes and DC-side inverter protection (Type 2 DC)
  • Buildings with external lightning protection or overhead supply lines (Type 1+2)

Technical specifications

Type 2 AC SPD
Poles1P+N / 3P+N
Nominal AC voltage Uo / Un230 V (50/60 Hz)
Max. continuous operating voltage Uc (L-N)275 V (1P+N) / 385 V (3P+N)
Max. continuous operating voltage Uc (N-PE)255 V
Nominal discharge current In (8/20 µs)40 kA
Maximum discharge current Imax (8/20 µs)40 kA
Open circuit voltage Uoc (1.2/50 µs)6 kV
Voltage protection level Up (L-N / N-PE)1.5 kV / 1.5 kV (1P+N); 1.8 kV / 1.5 kV (3P+N)
Response time tA (L-N / N-PE)<25 ns / <100 ns
Follow current interrupt rating If (N-PE)100 ARMS
Max. backup fuse125 A gG
Short-circuit current rating ISCCR (L-N)25 kA
TOV withstand UT (L-N)335 V (5 s); 440 V (120 min)
TOV withstand UT (N-PE), 200 ms1200 V
Type 1+2 AC SPD
Poles1P+N / 3P+N
Nominal AC voltage Uo / Un230 V (50/60 Hz)
Max. continuous operating voltage Uc (L-N)275 V (1P+N) / 385 V (3P+N)
Max. continuous operating voltage Uc (N-PE)255 V
Impulse discharge current Iimp (10/350 µs)12.5 kA
Total discharge current Itotal (10/350 µs)25 kA (1P+N) / 40 kA (3P+N)
Nominal / maximum discharge current (8/20 µs)40 kA / 40 kA
Specific energy W/R39 kJ/Ω
Charge Q6.25 As
Voltage protection level Up (L-N / N-PE)1.5 kV / 1.5 kV (1P+N); 1.8 kV / 1.5 kV (3P+N)
Response time tA (L-N / N-PE)<25 ns / <100 ns
Max. backup fuse250 A gG
Short-circuit current rating ISCCR (L-N)25 kA
TOV withstand UT (L-N)335 V (5 s); 440 V (120 min)
Type 2 DC SPD
Poles2P / 3P
Max. continuous operating voltage Ucpv600 V DC (2P) / 1000 V DC (3P)
Nominal discharge current In (8/20 µs)20 kA
Maximum discharge current Imax (8/20 µs)40 kA
Total discharge current Itotal (8/20 µs)40 kA
Voltage protection level Up2.2 kV (2P) / 4.0 kV (3P)
Residual current IPE<0.5 mA
Response time tA<25 ns
Short-circuit current rating Iscpv10 kA
Mechanical and environmental
Operating temperature-40 °C to +85 °C
Operating humidity5% to 95%
Altitude-500 m to 2000 m (80 kPa to 106 kPa)
Terminal screw torque2.5 Nm
Conductor cross section (max.)35 mm² solid/stranded, 25 mm² flexible
Mounting35 mm DIN rail, EN 60715
Degree of protectionIP20 (built-in)
Housing materialThermoplastic, UL 94 V-0
Remote contact conductor (max.)1.5 mm² solid (16 AWG)

Datasheets & brochures

↓ Manufacturer catalogue (PDF)